Edwards Signaling eFSA250 User Manual
Page 114

Chapter 2: Front panel programming
102
E-FSA64 and E-FSA250 Technical Reference Manual
Option
Description
Genesis non-silence: For Genesis and Enhanced Integrity horns and
strobes. Genesis and Enhanced Integrity appliances maintain
synchronization per UL 1971. For Genesis devices only, connected horns
cannot be silenced and strobes on the same two-wire circuit flash until the
panel is reset.
Genesis audible silence: For Genesis and Enhanced Integrity horns and
strobes. Genesis and Enhanced Integrity appliances maintain
synchronization per UL 1971. For Genesis devices only, it allows
connected horns to be silenced while strobes on the same two-wire circuit
continue to flash until panel reset.
Continuous silenceable: For strobes and notification appliances that self-
generate a temporal pattern
Continuous non-silenceable: For strobes and notification appliances that
self-generate a temporal pattern
Supervised: Lets you connect supervisory devices, such as a relay device
or switch
City tie: Outputs an unsynchronized, 24-volt continuous (steady) signal
that cannot be silenced or disabled. Select this NAC type when the NAC is
connected to a city tie module.
To program an input or output device:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Device.
4. If the panel has multiple loops, choose the loop to
be configured.
5. Enter the device address to be configured.
Note:
The device label occupies two lines just
below the device label.
6. Program each device in the system using Table 26
on page 95.
Note:
If you chose a dual address device, both
addresses for the device are displayed on the
screen (e.g. 001/002). The first address listed is
the device address you are programming. When
you pick the second address to program, both
addresses are still displayed but the order is
reversed (e.g. 002/001).
Loop Configuration
Loop class
Zone
Correlation Groups
Device
Device
Loop 01<>
Device
Number 001
Device label line 1
Device label line 2
Device 001
Zone 01<>
Label <>
Event notification
Correlation Groups
Day Sens Normal<>
Night Sens Normal<>
Day PreAlarm% 50<>
Night PreAlarm% 50<>
Base Type Sounder<>
Follow Alarm<>
Type Smoke<>