131
Table 37: Default loop event settings
Loop event
Printer
Dialer
NET (1-8) CID
Loop 1 initialization
Yes
None
No
n/a
Loop 1 fault (disable)
Yes
None
No
n/a
Loop 1 fault (trouble)
Yes
Acct 1
No
331
No
Loop 1 card fault (disable) (e.g. line fault)
Yes
None
No
n/a
Loop 1 card fault (trouble) (e.g. line fault)
Yes
Acct 1
No
333
Loop 1 Uncfgrd alarm (disable)
Yes
None
No
n/a
Loop 1 Uncfgrd alarm (trouble)
Yes
Acct 1
No
110
Loop 1 Uncfgrd trbl (disable)
Yes
None
No
n/a
Loop 1 Uncfgrd trbl (trouble)
No
None
No
n/a
Loop 1 over limits
Yes
None
No
n/a
Loop 1 address zero
Yes
None
No
n/a
Loop 2 initialization
Yes
None
No
000
Loop 2 fault (disable)
Yes
None
No
500
Loop 2 fault (trouble)
Yes
Acct 1
Yes
331
Loop 2 card fault (disable) (e.g. line fault)
Yes
None
No
500
Loop 2 card fault (trouble) (e.g. line fault)
Yes
Acct 1
No
333
Loop 2 Uncfgrd alarm (disable)
Yes
None
No
500
Loop 2 Uncfgrd alarm (trouble)
Yes
Acct 1
No
110
Loop 2 Uncfgrd trbl (disable)
Yes
None
No
500
Loop 2 Uncfgrd trbl (trouble)
No
None
No
331
Loop 2 over limits
Yes
None
No
331
Loop 2 address zero
Yes
None
No
331
To program loop events:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Loop Events.
4. Select the loop event.
5. Choose Event Notification.
Advanced Program
Panel Operation
Panel Events
Loop Events
Loop Events
Loop 1 Initializing
Loop 1 Fault
Loop 1 Map Fault