Edwards Signaling eFSA250 User Manual
Page 122

Chapter 2: Front panel programming
110
E-FSA64 and E-FSA250 Technical Reference Manual
Notes
• The option “CMS device” is only available if a dialer or network card is
installed
• The option “Printer” is only available if a printer (RS-232) card is installed
• The options “IP”, “MSK”, and “GWY” are only available if a network card is
installed
To program panel configuration options:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2
password.
3. Choose Panel Configuration.
4. Program the options.
Main Menu
Reports
Test
Control
Program
Program
Incremental Program
Auto Program
Advanced Program
Advanced Program
Loop Configuration
Panel Configuration
Panel Operation
NAC programming
The NAC circuits connected to the system must be programmed with the type of
NAC, label, correlation groups, and event notification. Each NAC must be
programmed separately.
Table 30: NAC programming options
Option
Description
Class
Select either Class A or Class B.
Note:
NAC 3 and 4 cannot be set to Class A. If NAC 1 and 2
are set to Class A, NAC 3 and 4 automatically configure to
accept the Class A return.