Clearing the event history log – Edwards Signaling eFSA250 User Manual
Page 68

Chapter 2: Front panel programming
56
E-FSA64 and E-FSA250 Technical Reference Manual
12. Press the Menu button to exit menu mode. The
button is now programmed to activate, disable, or
restore all correlation groups that you have added
to the list.
Clearing the event history log
The panel maintains a log of 1,000 system or user events. The event record
contains the event time, the event type, the event state, and the event ID. The
event time is the time and date of the event activation or restoration. All of these
records are stored in the panel’s history database and can be cleared (deleted) if
needed.
Once the history log is cleared, all new panel events are stored in history. You
might want to clear the history log in the following situations:
• When installation is complete, you can clear the history log before turning the
system over to the building owner.
• If the system history log is filled with event records resulting from a faulty
device, problem, or situation, you can clear the history log after the problem is
addressed.
Note: When the history log is full, the oldest event is deleted when a new event
is added.
To clear the event history log:
1. Press the Menu button and choose Program.
2. Choose Clear History.
3. Enter a level two password.
4. Select Yes to clear history or No to leave history
unchanged.
5. Press Enter.
6. Press the Menu button to exit menu mode, or
continue programming.
Main Menu
Reports
Test
Control
Program
Program
Advanced Program
Date and Time
Clear History
Enter Password
0000
Clear History
Yes
No