beautypg.com

Edwards Signaling Genesis Remote Mount Signal Master Module User Manual

Description, Installation

background image

© 2013 UTC Fire & Security. All rights reserved.

1 / 4

P/N 3100299 • REV 07 • REB 30JAN13

Genesis Remote Mount Signal Master Module
Installation Sheet

Description

The Genesis Remote Mount Signal Master Module provides
precision synchronization and independent horn control for
Genesis strobes and horns. Model numbers are listed below.

Table 1: Models

Description

Numbers

Genesis Remote Mount
Signal Master Module [1]

ADTG1M-RM,
G1M-RM
XLSG1M-RM

EG1M-RM
MG1M-RM
ZG1M-RM

[1] This module is compatible with Genesis, Enhanced Integrity
(synchronized), and Audible Detector base devices. For specific
models and quantities, see the compatibility list referenced on the
control panel.

Installation

Install in accordance with applicable requirements in the latest
editions of the NFPA codes and standards and Canadian
Electrical Code
, Part 1, Section 32, and in accordance with the
local authorities having jurisdiction.

Notes

The Genesis Remote Mount Signal Master Module is
shipped from the factory as an assembled unit; it contains
no user-serviceable parts and should not be
disassembled.

The Signal Master Module only synchronizes appliances
that are electrically connected to it and are electrically
downstream of it

Only one module is required for each notification
appliance circuit.

The strobe circuit of the module requires a dedicated NAC
whereas the horn circuit of the module can be cascaded
with other Genesis Signal Master modules on one NAC.

The strobe circuit must be continuous in alarm mode.

When determining allowable wire resistance, refer to the
voltage rating of the module, the signaling appliance, and
the control panel specifications.

To install the module:

1. Verify that all field wiring is free of opens, shorts, and

ground faults.

2. Make all wiring connections as shown in Figure 2 through

Figure 4.

3. Using the 4-24 x 1/2 in. screw, mount the wall plate on the

module as shown in Figure 1.

4. Using the two 6-32 x 1/2 machine screws, mount the

module in the electrical box.

Figure 1: Mounting in a single-gang box

1.

Compatible electrical box

2.

Remote Signal Master
Module

3.

Wall plate

4.

6-32 x 1/2 in. screw

5.

4-24 x 1/2 in. screw

55

1

2

4

4

3