Disabling and enabling panel NACs
Disabling a panel NAC prevents activations from being displayed, printed, or
reported off premises. This is typically done during maintenance. Remember to
enable the NAC as soon as you have finished working.
NACs that have been disabled are not restored when the panel is reset. They
must be enabled and then restored.
NACs configured as latched output devices are not restored when the panel is
reset. They must be manually unlatched and then restored.
When you disable a panel NAC:
• The common Disable LED turns on
• The LCD displays a message indicating that the NAC is disabled
• The disabled and active points indicators on the LCD increment
• The common Trouble LED flashes and the panel goes into a trouble state
• The common Trouble relay changes state.
To disable or enable a panel NAC:
1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Enable/Disable.
4. Choose Panel NAC.
5. Select the NAC that you want to disable or enable.
6. Press Enter.
The NAC is disabled and a message indicating
that the NAC is disabled is displayed on the LCD.
7. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Main Menu
Reports
Test
Control
Program
Enter Password
0000
Control
Enable/Disable
Activate/Restore
Enable/Disable
Panel Event
Loop Event
Panel NAC
Panel NAC Disable<>
1
NAC 1