Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
41
Table 8: Contact ID event codes
Event
CID
AC power (disable)
500
AC power (trouble)
301
Alarm active
110
Annunciator trouble
334
Aux. power 1 (disable)
500
Aux. power 1 (trouble)
312
Aux. power 2 (disable)
500
Aux. power 2 (trouble)
312
Battery charger (disable)
500
Battery charger (trouble)
309
Battery low (disable)
500
Battery low (trouble)
302
Battery missing (disable)
500
Battery missing (trouble)
311
Clear history
621
Common alarm
110
Common disable
500
Common monitor
140
Common supervisory
200
Common trouble
373
Common trouble for network dialer 373
Common trouble for telco dialer
373
Date
625
Device trouble
373
Device disable
570
Device pre alarm
118
Device alarm verify
118
Device maintenance alert
393
Device test
614
Dialer disable/remote disconnect
551
Event
CID
Dialer line 1 fault (disable)
500
Dialer line 1 fault (trouble)
351
Dialer line 2 fault (disable)
500
Dialer line 2 fault (trouble)
352
Dialer deliver fail
354
Dialer normal test
602
Dialer abnormal test
608
Dialer configuration
354
Drill
601
Duct active
116
Ground fault (disable)
500
Ground fault (trouble)
310
Heat active
114
Internal fault
307
IP Gateway Trouble
354
Loop 1 initialization
000
Loop 1 fault (disable)
500
Loop 1 fault (trouble)
331
Loop 1 card fault (disable)
500
Loop 1 card fault (trouble)
333
Loop 1 Uncfgrd alarm (disable)
500
Loop 1 Uncfgrd alarm (active)
110
Loop 1 Uncfgrd trbl (disable)
500
Loop 1 Uncfgrd trbl (trouble)
331
Loop 1 over limits
331
Loop 1 address zero
331
Loop 2 initialization
000
Loop 2 fault (disable)
500
Loop 2 fault (trouble)
331
Loop 2 card fault (disable)
500
Loop 2 card fault (trouble)
333