Chapter 2: Front panel programming
E-FSA64 and E-FSA250 Technical Reference Manual
63
Option
Description
Event notification
Configures event reporting for zones, individual devices, or both.
Zone: When a device is a member of a zone, only the zone information is
sent to the LCD, LEDs, printer, and dialer. Device level reporting
configuration is not available.
Zone/device: Zone information is sent to the LCD and LEDs. Device
information is sent to the printer and dialer. Zone/device reporting
locations can be configured through custom programming.
Device: Only device information is reported, no zone information
Label devices
Configures the auto programming sequence to allow you to label devices
using the alphanumeric keypad.
Yes: Enables device labeling
No: Disables device labeling
Label zones
Configures the auto programming sequence to allow you to label zones
using the alphanumeric keypad.
Yes: Enables zone labeling
No: Disables zone labeling
Follow
This option controls the conditions that will activate relay or sounder
detector bases. Select from the following values.
Head: The base is controlled by the detector’s settings.
• The base activates when the detector goes into alarm, unless the
detector is set for alarm verification.
• If the detector is set for alarm verification, the base activates when the
detector goes into alarm verification. It does not restore, however,
until the alarm restores.
• The base does not respond when the detector goes into prealarm no
matter how the detector is configured. Also, the base only follows the
primary element of a dual element detector. Any activation from a
secondary element does not trigger the base.
• Devices with the base set to follow Head cannot be placed in
correlation groups. When a device base is set to follow Head, the
base is removed as an output from any correlation groups to which it
belongs.
Alarm: The base activates its relay when the detector goes into alarm.
The base will not restore until the alarm event has been restored.
Alarm and verify (ALM+VFY): The base activates its relay when the
detector goes into alarm verify and continues when the detector goes into
alarm. The base will not restore until both events have been restored.
Alarm and prealarm (ALM+PALM): The base activates its relay when the
detector goes into prealarm and continues when the detector goes into an
alarm. The base will not restore until both events have been restored.
Riser: The base is triggered individually by the loop controller (sounder