Activating and restoring panel NACs
Activating a notification appliance circuit (NAC) turns on its outputs. Restoring the
NAC turns them off again. This is typically done for testing purposes.
Note:
Disabled NACs must be manually enabled and then restored. See
“Activating and restoring sensor bypass” on page 168.
To activate a panel NAC:
1. Press the Menu button and choose Control.
2. Enter a level one password.
3. Choose Activate/Restore.
4. Choose Panel NAC.
5. Select the NAC that you want to activate.
6. Press Enter.
7. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Main Menu
Reports
Test
Control
Program
Enter Password
0000
Control
Enable/Disable
Activate/Restore
Activate/Restore
Device
Panel NAC
Sensor Bypass
Gas Accel Response
Panel NAC Activate<>
1
NAC 1
Notes
• Disabled devices must be manually enabled and then restored. See
“Activating and restoring sensor bypass” on page 168.
• Latched output devices must be manually unlatched and then restored. See
“Unlatching latched output device” on page 164.