11.3 Motor changeover
Drive Functions
456
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
● 4 drive data sets (DDS), p0180 = 4
● 4 digital outputs to control the auxiliary contactors
● 4 digital inputs to monitor the auxiliary contactors
● 2 digital inputs for selecting the data set
● 4 auxiliary contactors with auxiliary contacts (1 NO contact)
● 4 motor contactors with positively-driven auxiliary contacts (3 NC contact, 1NO contact)
● 4 motors, 1 Control Unit, 1 infeed, and 1 Motor Module
.+
.
.
.
.
.
.+
.+
.+
.
.
.
.
.
.
.
.
.
.
.
U
U
S
6
.+
.+
.+
.+
6
S
U
U
U
S>@
S>@
S>@
S>@
.
.
.
.
Figure 11-2 Example of motor changeover
Table 11-3 Settings for the example
Parameter
Settings
Remark
p0130
4
Configure 4 MDS
p0180
4
Configure 4 DDS
p0186[0..3]
0, 1, 2, 3
The MDS are assigned to the DDS.
p0820, p0821
Digital inputs DDS
selection
p0822 to p0824
0
The digital inputs for motor switchover via DDS
selection are selected. Binary coding is used
(p0820 = bit 0 etc.).
p0826[0..3]
1, 2, 3, 4
Different numbers indicate a different thermal model
p0827[0..3]
1, 2, 3, 4
The bits of p0830 are assigned to the MDS. If
p0827[0] = 1, for example, bit p0830.1 is set when
MDS0 is selected via DDS0.
p0830.1 to
p0830.4
Digital outputs, auxiliary
contactors
The digital outputs for the auxiliary contactors are
assigned to the bits.
p0831[0..3]
Digital inputs, auxiliary
contacts
The digital inputs for the feedback signal of the motor
contactors are assigned.