Description of faults and alarms
Note
The faults and alarms for SINAMICS Safety Integrated are described in the following
documentation:
References: /LH1/ SINAMICS S List Manual
9.8
Acceptance test and certificate
9.8.1
General information about acceptance
Acceptance test
The machine manufacturer must carry out an acceptance test for the activated Safety
Integrated functions (SI functions) on the machine.
During the acceptance test, all the limit values entered for the enabled SI functions must be
exceeded to check and verify that the functions are working properly.
NOTICE
The acceptance test must only be carried out after the safety functions have been
commissioned and POWER ON reset.
Authorized person, acceptance report
Each SI function must be tested and the results documented and signed in the acceptance
certificate by an authorized person. The acceptance certificate must be stored in the
machine logbook.
Authorized in this sense refers to a person who has the necessary technical training and
knowledge of the safety functions and is authorized by the machine manufacturer to carry
out the test.
Note
•
The information and descriptions regarding commissioning must be carefully observed.
•
If any parameters are altered by SI functions, the acceptance test must be carried out
again and documented in the acceptance certificate.
•
Template for the acceptance certificate
A printed form is available in this manual as an example/suggestion.