Safety Integrated basic functions
9.1 General information
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
305
Password
The safety password protects the safety parameters against unauthorized write access.
In commissioning mode for Safety Integrated (p0010 = 95), you cannot change safety
parameters until you have entered the valid safety password in p9761 for the drives or
p10061 for the TM54F.
● When Safety Integrated is commissioned for the first time, the following applies:
– Safety password = 0
– Default setting for p9761 = 0
In other words:
The safety password does not need to be set during initial commissioning.
● In the case of a series commissioning of Safety or in the case of spare part installation,
the following applies:
– The safety password is retained on the CF card and in the STARTER project.
– No safety password is required in the case of spare part installation.
● Change password for the drives
– p0010 = 95 Commissioning mode
– p9761 = Enter "old safety password".
– p9762 = Enter "new password".
– p9763 = Confirm "new password".
– The new and confirmed safety password is valid immediately.
● Change password for the TM54F
– p0010 = 95 Commissioning mode
– p10061 = Enter "Old TM54F Safety Password" (factory setting "0")
– p10062 = Enter "new password"
– p10063 = Acknowledge "new password"
– The new and acknowledged safety password is valid immediately.
If you need to change safety parameters but you do not know the safety password, proceed
as follows:
1. Set the entire drive unit (Control Unit with all connected drives/components) to the factory
setting.
2. Recommission the drive unit and drives.
3. Recommission Safety Integrated.
Parameter overview for password (see SINAMICS S List Manual)
● p9761 SI password input
● p9762 SI password new
● p9763 SI password acknowledgement
● p10061 SI password input TM54F