Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Drive Functions
396
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Field
Data type
Values
Comment
The format and number specify the adjoining space containing values in the telegram.
Data types in conformity with PROFIdrive Profile shall be preferred for write access. Bytes,
words and double words are also possible as a substitute.
Unsigned8
0x00 ... 0xEA
No. 0 ... 234
Limited by DPV1 telegram length
No. of values
Specifies the number of subsequent values.
Unsigned16
0x0000 ... 0x00FF
Meaning of error value
--> see table 4-29
Error values
The error values in the event of a negative response.
If the values make up an odd number of bytes, a zero byte is appended. This ensures the
integrity of the word structure of the telegram.
Unsigned16
0x0000 ... 0x00FF
Values
The values of the parameter for read or write access.
If the values make up an odd number of bytes, a zero byte is appended. This ensures the
integrity of the word structure of the telegram.
Error values in DPV1 parameter responses
Table 10-27 Error values in DPV1 parameter responses
Error
value
Meaning
Comment
Additional
info
0x00
Illegal parameter number
Access to a parameter which does not exist.
–
0x01
Parameter value cannot be changed Modification access to a parameter value which cannot be
changed.
Subindex
0x02
Lower or upper value limit exceeded Modification access with value outside value limits.
Subindex
0x03
Invalid subindex
Access to a subindex which does not exist.
Subindex
0x04
No array
Access with subindex to an unindexed parameter.
–
0x05
Wrong data type
Modification access with a value which does not match the
data type of the parameter.
–
0x06
Illegal set operation (only reset
allowed)
Modification access with a value not equal to 0 in a case
where this is not allowed.
Subindex
0x07
Description element cannot be
changed
Modification access to a description element which cannot
be changed.
Subindex
0x09
No description data
Access to a description which does not exist (the
parameter value exists).
–
0x0B
No operating priority
Modification access with no operating priority.
–
0x0F
No text array exists
Access to a text array which does not exist (the parameter
value exists).
–
0x11
Request cannot be executed due to
operating status
Access is not possible temporarily for unspecified reasons. –
0x14
Illegal value
Modification access with a value which is within the limits
but which is illegal for other permanent reasons
(parameter with defined individual values).
Subindex