beautypg.com

6 cooling system, 1 "cooling system" function module – Efficient Networks Siemens Sinamics S120 User Manual

Page 233

background image

Function modules

7.6 Cooling system

Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

233

7.6

Cooling system

7.6.1

"Cooling system" function module

Features

● Control and monitoring functions of a cooling unit
● Automatically activated when using water-cooled power units
● Evaluation of a leakage water sensor (p0266.4)
● Evaluation of a water flow sensor (p0266.5, p0260, p0263)
● Evaluation of a conductivity sensor (p0266.6, p0266.7, p0261, p0262)
● Monitoring the water intake temperature using internal temperature sensors
● Monitoring the flow rating using internal temperature sensors

Description

A cooling unit (RKA) is responsible for cooling the water and the (non) conductivity in the de-

ionized water cooling circuit of a water-cooled power unit. The cooling unit is controlled and

monitored from a PLC that is part of the cooling unit. The "cooling unit" function module

described here is used as an interface between the closed-loop control and the external

control (open-loop) (PLC) of the cooling unit.. The cooling unit is controlled via terminals (e.g.

Control Unit, TM31).