Page 414

Communication PROFIBUS DP/PROFINET IO
10.2 Communication via PROFIBUS DP
Drive Functions
414
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
10.2.2.4 SIMATIC HMI addressing
You can use a SIMATIC HMI as a PROFIBUS master (master class 2) to access SINAMICS
directly. With respect to SIMATIC HMI, SINAMICS behaves like a SIMATIC S7. For
accessing drive parameters, the following simple rule applies:
● Parameter number = data block number
● Parameter sub-index = bit 0 - 9 of data block offset
● Drive object number = bit 10 - 15 of data block offset
Pro Tool and WinCC flexible
The SIMATIC HMI can be configured flexibly with "Pro Tool" or "WinCC flexible".
The following specific settings for drives must be observed when configuration is carried out
with Pro Tool or WinCC flexible.
Controllers: Protocol always "SIMATIC S7 – 300/400"
Table 10-29 Other parameters
Field
Value
Network parameter profile
DP
Network parameter baud rate
Any
Communication partner address
PROFIBUS address of the drive unit
Communication partner
slot/subrack
don’t care, 0
Table 10-30 Tags: "General" tab
Field
Value
Name
Any
Control
Any
Type
Depending on the addressed parameter value,
e.g.:
INT: for integer 16
DINT: for integer 32
WORD: for unsigned 16
REAL: for float
Area
DB
DB
(data block number)
Parameter number
1 ... 65535
DBB, DBW, DBD
(data block offset)
Drive object no. and subindex
Bit 15 – 10: Drive object no. 0 ... 63
Bit 9 – 0: Sub-index 0 ... 1023
In other words:
DBW = 1024 * drive object no. + sub-index
Length
Not activated
Acquisition cycle
Any