Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
365
Abbreviation
Name
Signal
number
Data type
1)
Comment
MELDW
Message word
102
U16
r2089[2] (bit
serial)
2)
MSOLL_GLATT
Total speed setpoint
120
I16
r00079[1]
AIST_GLATT
Torque utilization
121
I16
r0081
MT_ZSW
Status word for probe
131
U16
r0688
MT1_ZS_F
Probe 1 measuring time, falling edge
132
U16
r0687[0]
MT1_ZS_S
Probe 1 measuring time, rising edge
133
U16
r0686[0]
MT2_ZS_F
Probe 1 measuring time, falling edge
134
U16
r0687[1]
MT2_ZS_S
Probe 2 measuring time, rising edge
135
U16
r0686[1]
AKTSATZ
Pos selected block
202
U16
r2670
PosZSW
Pos status word
204
U16
r2683
XistP
Pos position actual value
206
U16
r2521
FAULT_CODE
Fault code
301
U16
r2131
WARN_CODE
Alarm code
303
U16
r2132
E_ZSW1
Status word for INFEED
321
U16
r899, r2139
(bit serial)
2)
CU_ZSW
Status word for Control Unit (CU)
501
U16
r2089[1]
1) Data type according to the PROFIdrive profile V4:
I16 = Integer16, I32 = Integer32, U16 = Unsigned16, U32 = Unsigned32
2) Bit-serial interconnection: Refer to the following pages, r2089 via binector-connector converter
STW1 (status word 1)
See function diagram [2452]
Table 10-11 Description of STW1 (status word 1)
Bit
Meaning
Comments
BICO
1
Ready to start
Power supply on, electronics initialized, line
contactor released if necessary, pulses inhibited.
0
Ready to power-up
0
Not ready to start
BO: r0899.0
1
Ready to operate
Voltage at Line Module (i.e. line contactor closed (if
used)), field being built up.
1
Ready to run
0
Not ready to operate
Reason: No ON command has been issued.
BO: r0899.1
1
Operation enabled
Enable electronics and pulses, then ramp up to
active setpoint.
2
Operation enabled
0
Operation inhibited
BO: r0899.2