2 commissioning, 3 integration – Efficient Networks Siemens Sinamics S120 User Manual
Page 225

Function modules
7.3 Extended monitoring functions
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
225
7.3.2
Commissioning
The extended monitoring functions are activated while the commissioning Wizard is running.
Parameter r0108.17 indicates whether it has been activated.
7.3.3
Integration
The extended monitoring functions are integrated as follows in the system.
Function diagrams (see SINAMICS S List Manual)
● 8010 Speed messages
● 8013 Load monitoring
Overview of key parameters (see SINAMICS S List Manual)
Load monitoring
● p2181[D] Load monitoring response
● p2182[D] Load monitoring speed threshold 1
● p2183[D] Load monitoring speed threshold 2
● p2184[D] Load monitoring speed threshold 3
● p2185[D] Load torque monitoring torque threshold 1 upper
● ...
● p2190[D] Load torque monitoring torque threshold 3 lower
● p2192[D] Load monitoring delay time
Speed setpoint monitoring
● p2150[D] Hysteresis speed 3
● p2151[C] CI: Speed setpoint
● p2161[D] Speed threshold value 3
● r2198.4 BO: ZSW monitoring 2, |n_setp| ≤ p2161
● r2198.5 BO: ZSW monitoring 2, n_setp < 0