Communication PROFIBUS DP/PROFINET IO
10.1 Communications according to PROFIdrive
Drive Functions
352
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
Drive object
Telegrams (p0922)
TM31
No predefined telegram.
TM41
3, 999
TB30
No predefined telegram.
CU_S
390, 391, 392, 999
Depending on the drive object, the following maximum number of process data items can be
transmitted for user-defined telegram structures:
Drive object
Max. number of PZD for sending / receiving
•
A_INF
Send 8, receive 5
•
B_INF
Send 8, receive 5
•
S_INF
Send 8, receive 5
•
SERVO
Send 19, receive 16
•
VECTOR
32
•
TM15DI/DO
5
•
TM31
5
•
TM41
Send 19, receive 16
•
TB30
5
•
CU
Send 15, receive 5
Interface Mode
Interface Mode is used for adjusting the assignment of the control and status words in line
with other drive systems and standardized interfaces.
The mode can be set as follows:
Value
Interface Mode
p2038 = 0
SINAMICS (factory setting)
p2038 = 1
SIMODRIVE 611 universal
p2038 = 2
VIK-NAMUR
Procedure:
1. Set p0922 ≠ 999.
2. p2038 = set required interface mode.
When you set a telegram from the range between 100 and 199, Interface Mode is set by
default (p2038 = 1) and cannot be changed.
Interface Mode defines the setting of the standard telegram 20 (p2038 = 2). The assignment
cannot be modified.
When a telegram that specifies the Interface Mode (e.g. p0922 = 102) is changed to a
different telegram (e.g. p0922 = 3), the setting in p2038 is retained.