Efficient Networks Siemens Sinamics S120 User Manual
Page 321

Safety Integrated basic functions
9.7 Commissioning the "STO", "SBC" and "SS1" functions
Drive Functions
Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4
321
No.
Parameter
Description/comments
5
p9652 > 0
p9852 > 0
Enable "Safe Stop 1" function.
Enable "SS1" on the Control Unit
Enable "SS1" on the Motor Module
•
The parameters are not changed until safety commissioning mode has been exited
(i.e. when p0010 ≠ 95 is set).
•
Both parameters are included in the crosswise data comparison and must, therefore,
be identical.
•
The "Safe Stop 1" function is not activated until at least one safety monitoring function
has been enabled (i.e. p9601 = p9801 ≠ 0).
6
p9620 = "Value"
Terminal "EP"
Set terminals for "Safe torque off (STO)".
Set the signal source for STO on the Control Unit.
Wire terminal "EP" (enable pulses) on the Motor Module.
•
Control Unit monitoring channel:
By appropriately interconnecting BI: p9620 for the individual drives, the following is
possible:
– Selecting/deselecting the STO
– Grouping the terminals for STO
•
Motor Module monitoring channel:
By wiring the "EP" terminal accordingly on the individual Motor Modules, the following
is possible:
– Selecting/deselecting the STO
– Grouping the terminals for STO
Note:
The STO terminals must be grouped identically in both monitoring channels.
7
p9650 = "Value"
p9850 = "Value"
Set F-DI changeover tolerance time.
F-DI changeover tolerance time on Control Unit
F-DI changeover tolerance time on Motor Module
•
The parameters are not changed until safety commissioning mode has been exited
(i.e. when p0010 ≠ 95 is set).
•
Due to the different runtimes in the two monitoring channels, an F-DI changeover
(e.g., selection/deselection of STO) does not take immediate effect. After an F-DI
changeover, dynamic data is not subject to a data cross-check during this tolerance
time.
•
Both parameters are included in the crosswise data comparison and must, therefore,
be identical. A difference of one safety monitoring clock cycle is tolerated for the
values.