beautypg.com

3 active infeed closed-loop control chassis – Efficient Networks Siemens Sinamics S120 User Manual

Page 24

background image

Infeed

1.1 Active Infeed

Drive Functions

24

Function Manual, (FH1), 07/2007 Edition, 6SL3097-2AB00-0BP4

1.1.3

Active Infeed closed-loop control Chassis

Schematic structure

6XSSO\V\VWHPGDWD

0DQLSXODWHG
YDULDEOHV

$FWXDOYDOXHV

'&OLQN

6XSSO\V\VWHP

)XVHV

0DLQVZLWFK

$FWLYH,QWHUIDFH0RGXOH

ZLWKSUHFKDUJLQJ

ZLWK960

:LWKOLQHILOWHU

ZLWKOLQHUHDFWRU

'5,9(&/L4

,QIHHG

$FWLYH

)LUPZDUH

&RQWURO8QLW

$FWLYH/LQH0RGXOH

&KDVVLV

Figure 1-2

Schematic structure of Active Infeed

Operating mode of Active Infeed closed-loop control for Chassis Active Line Modules.

Active Line Modules Chassis only function in Active Mode.
In Active Mode, the DC link voltage is regulated to a variable setpoint (p3510), which results

in a sinusoidal line current (cosφ = 1).
The DC link voltage setpoint (p3510) is preset depending on the supply voltage (p0210)

using the equation p3510 = 1.5 * p0210.

Commissioning

The device supply voltage (p0210) must be parameterized during commissioning. The

necessary line filter (p0220) is preset.
When it is first switched on with a new/modified network, an automatic controller setting

should be implemented using the line/DC link identification routine (p3410).

Note
In a supply system without regenerative feedback capability (e.g. generators), regenerative

operation must be inhibited via the binector input p3533.

The DC link voltage (p3510) can be set within the following limits:
● Upper limit:

– Maximum DC link voltage (p0280)
– Product of line voltage (p0210) and max. step-up factor (r3508)

● Lower limit: Supply voltage (p0210) multiplied by 1.42