Technical Specifications
Appendix B
Certifications
The PowerMonitor 5000 unit adheres to the following certifications and
approvals.
UL/CUL
UL 61010 listed, File E345550, for Measuring, Testing and Signal-generation
Equipment and CUL Certified.
CE Certification
If this product bears the CE marking, it is approved for installation within the
European Union and EEA regions. It has been designed to meet the following
directives.
Table 195 - General Specifications
Parameter
Maximum Rating
Voltage Terminal Blocks
18…14 AWG (0.75…2.5 mm
2
), 75 °C Minimum Copper
Wire only Recommended torque 1.5 N•m (13.3 lb•in)
Current Sensing Input
12 AWG (4 mm
2
), 75 °C Minimum Copper Wire only
Recommended torque: N/A
Control Power Terminal Block
22…14 AWG (0.25…2.5 mm
2
), 75 °C Minimum Copper
Wire only Recommended torque 0.63 N•m (5.6 lb•in)
Input/Output (I/O) Terminal Block
20…14 AWG (0.5…2.5 mm
2
), 75 °C Minimum Copper
Wire only Recommended torque 0.63 N•m (5.6 lb•in)
Temperature, Operating
-20…70 °C (4…158 °F)
Temperature, Storage
-40…85 °C (-40…185 °F)
Humidity
5…95%, Noncondensing
Vibration
2 g
Shock, Operating
30 g
Shock, Nonoperating
50 g
Dielectric Withstand
UL61010, EN61010
Installation Location
Indoor use only
Altitude
Max 2000 m (6560 ft.)