Install the PowerMonitor 5000 Unit

Chapter 2

Figure 15 - Diagram I3 - 3-phase, 3- or 4-wire, 3 CTs

Status Inputs

Up to four dry (non-powered) contacts can be connected to the
PowerMonitor 5000 unit status inputs. The status input derives 24V DC power
from its internal power supply.

Connect status inputs by using shielded, twisted-pair cable with the shield
connected to the ground bus or other low-impedance earth ground at the contact
end only. The diagram indicates typical status input wiring.

Figure 16 - Status Inputs

L1

L2

L3

Line

CTs (by user)

CT1

CT2

CT3

CT4

(if

used)

Load

Ground

Shorting Terminal

Block (by user)

Metering_Mode = Wye, Delta 3 CT, Open Delta 3 CT,

Delta Grd B Ph 3 CT, or Delta High-leg, as applicable