Loggingresults.triggerdata_header (m6 model), Loggingresults. triggerdata_header data table – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 347
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
347
PowerMonitor 5000 Unit Data Tables
Appendix A
LoggingResults.TriggerData_Header (M6 model)
Table 165 - Table Properties
CIP Instance Number
862
PCCC File Number
F71
No. of Elements
15
Length in Words
30
Data Type
Real
Data Access
Read Only
Table 166 - LoggingResults. TriggerData_Header Data Table
Element
Number
Type
Tag Name
Description
Unit
Range
0
Real
Record_Indicator
Indicates the significance of data in the record
0 = No record returned
1= the record contains
parameter values
2 = the record contains general
information of the log file being
retrieved, reference to each item
description in the data table
3= log file not found
1
Real
TriggerHeader_Record
_Identifier
Internal unique record number, if Record_Indicator = 1
Total records number in the log file, if Record_Indicator = 2.
#
+/- 0…9.999E15
2
Real
TriggerAction_
Timestamp_Year
The year when the trigger action occurred.
YYYY
2010…2100
3
Real
TriggerAction_
Timestamp_Month_
Day
The month and day when the trigger action occurred.
MMDD
0110…1231
4
Real
TriggerAction_
Timestamp_Hour_
Minute
The hour and minute when the trigger action occurred.
hhmm
0000…2359
5
Real
TriggerAction_
Timestamp_Sec_mS
The seconds and milliseconds when the trigger action occurred.
ssmS
00000…59999
6
Real
SetpointNumber
Setpoint number of trigger
#
1…30
7
Real
ParameterSelection or
Logic_Gate_Type
ParameterSelection if SetpointNumber = (1…20)
Logic_Gate_Type if SetpointNumber = (21 …30)
#
See description
8
Real
ReferenceValue or
Logic_Input_1
ReferenceValue if SetpointNumber = (1…20)
Logic_Input_1 if SetpointNumber = (21… 30)
#
See description
9
Real
TestCondition or
Logic_Input_2
TestCondition if SetpointNumber = (1…20)
Logic_Input_2 if SetpointNumber = (21 …30)
#
See description
10
Real
EvaluationType or
Logic_Input_3
EvaluationType if SetpointNumber = (1…20)
Logic_Input_3 if SetpointNumber = (21…30)
#
See description
11
Real
Threshold or
Logic_Input_4
Threshold if SetpointNumber = (1… 20)
Logic_Input_4 if SetpointNumber = (21… 30)
#
See description
12
Real
Hysteresis
Hysteresis for setpoint
#
0…10,000,000
13
Real
AssertDelay_s
AssertDelay for setpoint
s
0.000…3600
14
Real
DeassertDelay_s
DeassertDelay for setpoint
s
0.000…3600