Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 294

294
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
2
Int16
Assembly_Slot_1_Status_Inst1
Backplane Processor(BF518) of Assembly in slot 1 Status 0 =
Status PASS
0…65,535
Bit0
NOR Flash
BF518 Nor flash read write failure
Bit1
SDRAM Memory
BF518 SDRAM memory failure
Bit2
Ethernet MAC
BF518 Ethernet MAC failure
Bit3
SPORT Communication
BF518 SPORT communication failure
Bit4
Sharc Heartbeat message Timeout
Shark Heartbeat message Timeout
Bit5
Backplane info. message Timeout
Backplane info. message Timeout
Bit6
ForwardOpen Message Not Received
PDA BF518 did not receive forward open message
Bit7
Real Time Data Not Received
PDA BF518 did not receive SHARC message
3
Int16
Assembly_Slot_1_Status_Inst2
Host Processor(Sharc) of Assembly in slot 1 Status
0 = Status PASS
0…65,535
Bit0
SDRAM Memory
Sharc SDRAM Memory failure
Bit1
AD7606
AD7606 failure
Bit2
SPORT Communication
Sharc SPORT communication failure
Bit3
MAN_CODE
Bit4
DEV_CODE
Bit5
NORFLASH
Sharc Nor flash read write failure
Bit6
RESET
Sharc Reset failure
4
Int16
Assembly_Slot_2_Status_Inst1
Backplane Processor of Assembly in slot 2 Status
0 = Status PASS
0…65,535
5
Int16
Assembly_Slot_2_Status_Inst2
Host Processor of Assembly in slot 2 Status
0 = Status PASS
0…65,535
6
Int16
Assembly_Slot_3_Status_Inst1
Backplane Processor of Assembly in slot 3 Status
0 = Status PASS
0…65,535
7
Int16
Assembly_Slot_3_Status_Inst2
Host Processor of Assembly in slot 3 Status
0 = Status PASS
0…65,535
8
Int16 Bootloader_FRN_Slot_0_Inst_1
MPC BF518 bootloader image revision number
0…65,535
9
Int16
Application_FRN_Slot_0_Inst_1
MPC BF518 application image revision number, if the system is
running the boot loader image because of application image
checksum error, this number is zero
0…65,535
10
Int16
Upgrader_FRN_Slot_0_Inst_1
MPC BF518 boot kernel image revision number
0…65,535
11
Int16 Bootloader_FRN_Slot_0_Inst_2
ARM9
boot level 0 image revision number
0…65,535
12
Int16
Application_FRN_Slot_0_Inst_2
ARM9 application image revision number
0…65,535
13 Int16
Upgrader_FRN_Slot_0_Inst_2 ARM9
boot level 1 image revision number
0…65,535
14 Int16
Bootloader_FRN_Slot_1_Inst_1 PDA
BF518
bootloader image revision number
0…65,535
15
Int16 Application_FRN_Slot_1_Inst_1 PDA
BF518
application image revision number, if the system is
running the boot loader image because of application image
checksum error, this number is zero
0…65,535
16
Int16
Upgrader_FRN_Slot_1_Inst_1
PDA BF518 boot kernel image revision number
0…65,535
17
Int16
Bootloader_FRN_Slot_1_Inst_2 SHARC
boot loader image revision number
0…65,535
18 Int16
Application_FRN_Slot_1_Inst_2
SHARC application image revision number
0…65,535
Table 106 - Status.RunTime Data Table
Element
Number
Type
Tag Name
Description
Range