Logging
Logged Parameters
The event log operates in a circular, or FIFO fashion. When accessed as a file, the
first record is a header containing the tag names. Each subsequent record is a
structure of REAL elements containing the following parameters.
Tag Name
Description
Record_Identifier
Used to verify record sequence when returning multiple records
Event_Type
Power quality event type, see Power Quality Event Code table.
Sub_Event_Code
Indicate the sub event of the event type. For example, a sag event can happen in V1, V2 or V3. See Power Quality Event Code table.
Local_Timestamp_Year
Year of the local time when the record was recorded
Local_Timestamp_Mth_Day
Month and Day of the local time when the record was recorded
Local_Timestamp_Hr_Min
Hour and Minute of the local time when the record was recorded
Local_Timestamp_Sec_mS
Second and Millisecond of the local time when the record was recorded.
Local_Timestamp_uS
Microsecond when the record was recorded
UTC_Timestamp_Year
Year of the UTC when the record was recorded
UTC_Timestamp_Mth_Day
Month and Day of the UTC when the record was recorded
UTC_Timestamp_Hr_Min
Hour and Minute of the UTC when the record was recorded.
UTC_Timestamp_Sec_mS
Second and Millisecond of UTC when the record was recorded.
UTC_Timestamp_uS
Microsecond of UTC when the record was recorded.
Association_Timestamp_Year
Year of the timestamp associated with waveform file if the event can trigger a waveform capture
Association_Timestamp_Mth_Day
Month and Day of the timestamp associated with waveform file if the event can trigger a waveform capture
Association_Timestamp_Hr_Min
Hour and Minute of the timestamp associated with waveform file if the event can trigger a waveform capture
Association_Timestamp_Sec_mS
Second and Millisecond of the timestamp associated with waveform file if the event can trigger a waveform capture
Association_Timestamp_uS
Microsecond of the timestamp associated with waveform file
Event_Duration_mS
Event duration in milliseconds for a sag or swell event, Event duration in cycles for WSB events
Min_or_Max_Volts
Minimum value of a sag or maximum value of a swell
Trip_Point
The trip point that triggered the event
WSB Originator
ID of the unit that originated the WSB message; the 3 least significant bytes of its MAC ID