beautypg.com

Configuration.log_read – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual

Page 281

background image

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

281

PowerMonitor 5000 Unit Data Tables

Appendix A

Configuration.Log_Read

Table 75 - Table Properties

CIP Instance Number

814

PCCC File Number

N23

No. of Elements

15

Length in Words

15

Data Type

Int16

Data Access

Read/Write

Table 76 - Configuration.Log_Read Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Int16

Selected Log

Selects the log that information is returned from. Once a single request has
been made the auto return feature brings back successive records each time the
log is read. Some logs support individual record requests.
1 = Unit Event Log
2 = Min/Max Log
3 = Load Factor Log
4 = Time of Use Log
5 = Setpoint Log
6 = Alarm Log
7 = Data Log File List
8 = Energy Log File List
9 = Trigger Data File
10 = Power Quality Log
11 = Waveform Log File
Important: If your catalog number does not support the requested log item,
the power monitor ignores the request. Check the Write Status Table.

1

1…11

1

Int16

Chronology of
Auto Return Data

The date chronology of the returned records.
0 = Reverse direction
1 = Forward direction.

1

0…1

2

Int16

The Min/Max
record to be
returned

Selects the Min/Max record number to be returned. See the table for Min/Max
record list.

0

0…82

3

Int16

Load Factor or
TOU record to be
returned.

Selects the Load Factor or TOU record number to be returned. 0 = Use
incremental return and the chronology selected. 1 through 13 selects an
individual record. 1 = Current record being calculated.

0

0…13

4…14

Int16

Reserved

Reserved for future use.

0

0