Configuration.log_read – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 281
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
281
PowerMonitor 5000 Unit Data Tables
Appendix A
Configuration.Log_Read
Table 75 - Table Properties
CIP Instance Number
814
PCCC File Number
N23
No. of Elements
15
Length in Words
15
Data Type
Int16
Data Access
Read/Write
Table 76 - Configuration.Log_Read Data Table
Element
Number
Type
Tag Name
Description
Default
Range
0
Int16
Selected Log
Selects the log that information is returned from. Once a single request has
been made the auto return feature brings back successive records each time the
log is read. Some logs support individual record requests.
1 = Unit Event Log
2 = Min/Max Log
3 = Load Factor Log
4 = Time of Use Log
5 = Setpoint Log
6 = Alarm Log
7 = Data Log File List
8 = Energy Log File List
9 = Trigger Data File
10 = Power Quality Log
11 = Waveform Log File
Important: If your catalog number does not support the requested log item,
the power monitor ignores the request. Check the Write Status Table.
1
1…11
1
Int16
Chronology of
Auto Return Data
The date chronology of the returned records.
0 = Reverse direction
1 = Forward direction.
1
0…1
2
Int16
The Min/Max
record to be
returned
Selects the Min/Max record number to be returned. See the table for Min/Max
record list.
0
0…82
3
Int16
Load Factor or
TOU record to be
returned.
Selects the Load Factor or TOU record number to be returned. 0 = Use
incremental return and the chronology selected. 1 through 13 selects an
individual record. 1 = Current record being calculated.
0
0…13
4…14
Int16
Reserved
Reserved for future use.
0
0