Chapter 6
Logging
Waveform Header
If the value of Record_Indicator is 2, the LoggingResults.Waveform_Log table
returns the following information. The data type returned is REAL, although
some elements (MAC ID) are better interpreted as UINT32.
If the waveform retrieval is interrupted for more than 60 seconds, the sequence
needs to be reinitialized by writing the Configuration.WaveformFileName table.
Appending the filename with selection switches configured for the next record in
sequence begins the retrieval where it left off before the interruption.
Waveform Recording (M6 model) on page 93
for more information
about waveform setup, operation, commands, related functions, and retrieval via
ftp and the native Ethernet port.
Element Number
Tag Name
Description
0
Record_Indicator
Indicates the significance of the data in the record 2 = the record contains general information of the log file
being retrieved, reference to each item description in the data table;
1
File_ID
The selected file ID
2
Waveform_Identifier_High
File ID (Int16)+ Waveform Identifier(Int48)
typedef struct
{
unsigned short sFileID; //this id is used for user selection, 1…256
unsigned short sWaveformID; //the Waveform id highest 2 bytes
unsigned long lWaveformID; //the Waveform id Lowest 4 bytes
}WAVEFORM_ID;
3
Waveform_Identifier_Low
4
Revision
Waveform file format revision
5
Compression
Indicate compression or not and the compression type, high 8 bits is compression flag , low 8 bits is
compression type
6
Metering_Mode
Metering mode, indicates voltages are L-N or L-L
7
Mac_Address_High
Mac address of power monitor - high 3 bytes
8
Mac_Address_High
Low 3 bytes
9…42
Reserved
Reserved for future use