Status.wiring_corrections – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 311
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
311
PowerMonitor 5000 Unit Data Tables
Appendix A
Status.Wiring_Corrections
Table 119 - Table Properties
CIP Instance Number
834
PCCC File Number
N43
No. of Elements
14
Length in Words
14
Data Type
Int16
Data Access
Read Only
Table 120 - Status.Wiring_Corrections Data Table
Element
Number
Type
Tag Name
Description
Default
Range
0
Int16
Wiring_Correction_Commands
0 = No command
1 = Correct wiring by using Range 1 results, Lagging 97 PF to Leading 89 PF
2 = Correct wiring by using Range 2 results, Lagging 85 PF to leading 98 PF
3 = Correct wiring by using Range 3 results, Lagging 52 PF to lagging 95 PF
4 = Correct wiring by using manual input parameters
5 = Remove all wiring corrections
0
0…5
1
Int16
Input_V1_Mapping
This parameter logically maps a physical voltage channel to V1.
1 = V1
2 = V2
3 = V3
-1 = V1 inverted
-2 = V2 inverted
-3 = V3 inverted
1
-3…-1
1…3
2
Int16
Input_V2_Mapping
This parameter logically maps a physical voltage channel to V2.
1 = V1
2 = V2
3 = V3
-1 = V1 inverted
-2 = V2 inverted
-3 = V3 inverted
2
-3… -1
1…3
3
Int16
Input_V3_Mapping
This parameter logically maps a physical voltage channel to V3.
1 = V1
2 = V2
3 = V3
-1 = V1 inverted
-2 = V2 inverted
-3 = V3 inverted
3
-3…-1
1 …3
4
Int16
Input_I1_Mapping
This parameter logically maps a physical current channel to I1.
1 = I1
2 = I2
3 = I3
-1 = I1 inverted
-2 = I2 inverted
-3 = I3 inverted
1
-3…-1
1…3