Configuration.Setpoints_6_10

Table 63 - Table Properties

CIP Instance Number

808

PCCC File Number

F17

No. of Elements

50

Length in Words

100

Data Type

Real

Data Access

Read/Write

Table 64 - Configuration.Setpoints_6_10 Data Table

Element
Number

Type

Tag Name

Description

Default

Range

0

Real

Parameter
Selection 6

Selection of the input parameter from the

Setpoint Parameter Selection List

.

0

0…105

1

Real

Input Reference
Selection 6

Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value

0

0

2

Real

Test Condition 6

0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals

0

0…3

3

Real

Evaluation Type 6

0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)

0

0…3

4

Real

Threshold 6

The value, percent or state that triggers the output action.

0

-10,000,000…
10,000,000

5

Real

Hysteresis 6

The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).

0

0…10,000,000

6

Real

Assert Delay
Seconds 6

The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.

0

0.000…3600

7

Real

Deassert Delay
Seconds 6

The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.

0

0.000…3600

8

Real

Parameter
Selection 7

Selection of the input parameter from the

Setpoint Parameter Selection List

.

0

0…105

9

Real

Input Reference
Selection 7

Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value

0

0

10

Real

Test Condition 7

0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals

0

0…3

11

Real

Evaluation Type 7

0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)

0

0…3

12

Real

Threshold 7

The value, percent, or state that triggers the output action.

0

-10,000,000…
10,000,000