Configuration.setpoints_6_10 – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 257
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
257
PowerMonitor 5000 Unit Data Tables
Appendix A
Configuration.Setpoints_6_10
Table 63 - Table Properties
CIP Instance Number
808
PCCC File Number
F17
No. of Elements
50
Length in Words
100
Data Type
Real
Data Access
Read/Write
Table 64 - Configuration.Setpoints_6_10 Data Table
Element
Number
Type
Tag Name
Description
Default
Range
0
Real
Parameter
Selection 6
Selection of the input parameter from the
Setpoint Parameter Selection List
0
0…105
1
Real
Input Reference
Selection 6
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
0
0
2
Real
Test Condition 6
0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0
0…3
3
Real
Evaluation Type 6
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
0
0…3
4
Real
Threshold 6
The value, percent or state that triggers the output action.
0
-10,000,000…
10,000,000
5
Real
Hysteresis 6
The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0
0…10,000,000
6
Real
Assert Delay
Seconds 6
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0
0.000…3600
7
Real
Deassert Delay
Seconds 6
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0
0.000…3600
8
Real
Parameter
Selection 7
Selection of the input parameter from the
Setpoint Parameter Selection List
0
0…105
9
Real
Input Reference
Selection 7
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
0
0
10
Real
Test Condition 7
0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0
0…3
11
Real
Evaluation Type 7
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
0
0…3
12
Real
Threshold 7
The value, percent, or state that triggers the output action.
0
-10,000,000…
10,000,000