Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
309
PowerMonitor 5000 Unit Data Tables
Appendix A
Status.OptionalComm
Table 117 - Table Properties
CIP Instance Number
835
PCCC File Number
N44
No. of Elements
30
Length in Words
30
Data Type
Int16
Data Access
Read Only
Table 118 - Status.OptionalComm Data Table
Element
Number
Type
Tag Name
Description
Units
Range
0
Int16
Network_Type
0x25 = DeviceNet
0x65 = ControlNet
-
0 …255
1
Int16
Firmware_Version
Optional communication firmware version
Network_
Type
dependent
0…255
2
Int16
Firmware_Build
Optional communication firmware build
Network_
Type
dependent
0
3
Int16
Serial_Number_Low
Low 16-bit serial number
-
0
4
Int16
Serial_Number_High
High 16-bit serial number
-
0
5
Int16
Optional_Port_Status
Bit15: Watchdog Timeout indicator
0: The application and ABCC communicate normally
1: The application lost the communication with ABCC module, so the watch dog times-out.
Bit14 to Bit5 reserved for future use.
Bit4: SUP bit
0: Module is not supervised;
1: Module is supervised.
Bit3 … Bit 0: Current status of Anybus module
000: SETUP
001: NW_INIT
010: WAIT_PROCESS
011: IDLE
100: PROCESS_ACTIVE
101: ERROR
110: reserved
111: EXCEPTION
-
0…7
6
Int16
Exception_Code
Last exception
0 = No exception
1 = Application timeout
2 = Invalid device address
3 = Invalid communication setting
4 = Major unrecoverable app event
5 = wait for reset
6 = Invalid process data config
7 = Invalid application response
8 = Non-volatile memory checksum error
Other value = reserved
-
0…8