Power quality log records can be retrieved in a file from the PowerMonitor 5000
web page or ftp server. The link for the power quality log is found in the
LoggingResults.General_Logs tab in the web page.
To retrieve the file, click the link and follow the prompts to save or open the file.
The ftp server works in a similar way.
Records can also be retrieved sequentially through the native Ethernet network
communication or an optional communication port by using the data table
interface. A read of the
table returns the number of power
quality log records in Element 15.
Select the power quality log and the desired order of record retrieval by writing
values to these tags in the
table.
•
Selected Log = 10, Power Quality Log
•
Chronology of Auto Return Data = 0 for most recent first (default), 1 for
earliest first
Successive reads of the
LoggingResults.Power_Quality_Log (M6 model)
table
return records in the selected sequence. After the last record is read, the next read
starts again from the end or beginning of the log as was selected.