Install the PowerMonitor 5000 Unit

Pay particular attention to the correct phasing and polarity of current sensing
connections. The diagrams use the ‘dot’ convention to indicate transformer
polarity. The dot indicates the H1 and X1 terminals on the primary and
secondary of the CT respectively. Phasing of the CTs must correspond to the
phasing of the voltage sensing connections.

The following wiring diagrams indicate typical current sensing connections to
various types of power systems.

Figure 13 - Diagram I1 - Split-phase, 2 CTs

Figure 14 - Diagram I2 - 3-phase, 3-wire, 2 CTs

L1

L2

N

(if used)

Line

CTs (by user)

CT1

CT2

CTN

(if used)

Load

Ground

Shorting Terminal

Block (by user)

Metering_Mode = Split-phase

PowerMonitor 5000

I1

I2

I3

I4

X1

X1

X1

X1

L1

L2

L3

Line

CTs (by user)

CT1

CT3

2 CTs Can Be Used Only

On 3-wire Systems

Load

Ground

Shorting Terminal

Block (by user)

Metering_Mode = Delta 2 CT, Open Delta 2 CT,

or Delta Grd B Ph 2 CT, as applicable

PowerMonitor 5000

I1

I2

I3

I4

X1

X1

X1

X1