Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 299
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
299
PowerMonitor 5000 Unit Data Tables
Appendix A
12
Real
Range2_Current_Rotation
Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…321
13
Real
Range3_L52_L95_Status
This is the pass fail status for Range 1 diagnostics.
0 = Pass
1 = Failed
0 or 1
14
Real
Range3_Voltage_Input_Inverted
Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
15
Real
Range3_Current_Input_Inverted
Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
16
Real
Range3_Voltage_Rotation
Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…132
17
Real
Range3_Current_Rotation
Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…321
18
Real
Voltage_Phase_1_Angle
Shows the present phase angle of this channel. Always 0 degrees for voltage phase 1.
0…359.99
19
Real
Voltage_Phase_1_Magnitude
Shows the present magnitude of this phase.
0…9,999,999
20
Real
Voltage_Phase_2_Angle
Shows the present phase angle of this channel.
0…359.99
21
Real
Voltage_Phase_2_Magnitude
Shows the present magnitude of this phase.
0 …9,999,999
22
Real
Voltage_Phase_3_Angle
Shows the present phase angle of this channel.
0…359.99
23
Real
Voltage_Phase_3_Magnitude
Shows the present magnitude of this phase.
0…9,999,999
24
Real
Current_Phase_1_Angle
Shows the present phase angle of this channel.
0…359.99
25
Real
Current_Phase_1_Magnitude
Shows the present magnitude of this phase.
0…9,999,999
26
Real
Current_Phase_2_Angle
Shows the present phase angle of this channel.
0…359.99
Table 110 - Status.Wiring_Diagnostics Data Table
Element
Number
Type
Tag Name
Description
Range