Configuration.powerquality – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 282
282
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
Configuration.PowerQuality
Table 77 - Table Properties
CIP Instance Number
815
PCCC File Number
F24
No. of Elements
50
Length in Words
100
Data Type
Real
Data Access
Read/Write
Table 78 - Configuration.PowerQuality Data Table
Element
Number
Type
Tag Name
Description
Default
Range
0
Real
Sag1_Trip_Point_%
The percent of Nominal System Voltage that creates a level 1 sag
condition.
90
0.00…100.00
1
Real
Sag1_Hysteresis_%
The percent of hysteresis for sag 1 condition.
2
0.00…10.00
2
Real
Sag2_Trip_Point_%
The percent of Nominal System Voltage that creates a level 2 sag
condition.
80
0.00…100.00
3
Real
Sag2_Hysteresis_%
The percent of hysteresis for sag 2 condition.
2
0.00…10.00
4
Real
Sag3_Trip_Point_%
The percent of Nominal System Voltage that creates a level 3 sag
condition.
70
0.00…100.00
5
Real
Sag3_Hysteresis_%
The percent of hysteresis for sag 3 condition.
2
0.00…10.00
6
Real
Sag4_Trip_Point_%
The percent of Nominal System Voltage that creates a level 4 sag
condition.
40
0.00…100.00
7
Real
Sag4_Hysteresis_%
The percent of hysteresis for sag 4 condition.
2
0.00…10.00
8
Real
Sag5_Trip_Point_%
The percent of Nominal System Voltage that creates a level 5 sag
condition.
5
0.00…100.00
9
Real
Sag5_Hysteresis_%
The percent of hysteresis for sag 5 condition.
2
0.00…10.00
10
Real
Swell1_Trip_Point_%
The percent of Nominal System Voltage that creates a level 1 swell
condition.
110
100.00…200.00
11
Real
Swell1_Hysteresis_%
The percent of hysteresis for swell 1 condition.
2
0.00…10.00
12
Real
Swell2_Trip_Point_%
The percent of Nominal System Voltage that creates a level 2 swell
condition.
120
100.00…200.00
13
Real
Swell2_Hysteresis_%
The percent of hysteresis for swell 2 condition.
2
0.00…10.00
14
Real
Swell3_Trip_Point_%
The percent of Nominal System Voltage that creates a level 3 swell
condition.
140
100.00…200.00
15
Real
Swell3_Hysteresis_%
The percent of hysteresis for swell 3 condition.
2
0.00…10.00
16
Real
Swell4_Trip_Point_%
The percent of Nominal System Voltage that creates a level 4 swell
condition.
180
100.00…200.00
17
Real
Swell4_Hysteresis_%
The percent of hysteresis for swell 4 condition.
2
0.00…10.00
18
Real
Capture_Pre_Event_Cycles
The pre-event cycles for waveform capture
5
5…10
19
Real
Capture_Post_Event_Cycles
The post-event cycles for waveform capture
15
2…30
20
Real
Relative_Setpoint_Intvl_m
The interval setting in minutes for the rolling average of all relative
setpoints.
60
1…1440
21
Real
IEEE1159_Parameter_Hysterisis_%
The percent of hysteresis for IEEE1159 output parameters.
2
0.00…10.00
22
Real
IEEE1159_Imbalance_Averaging_Intvl_m
The rolling average interval for Imbalance in minutes
15
15…60