Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 213
![background image](/manuals/578319/213/background.png)
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
213
Communication
Chapter 9
EDS Add-on Profile Connection (Native EtherNet/IP units only)
The PowerMonitor 5000 unit can be configured with an electronic data sheet
(EDS) based AOP (add-on profile) in RSLogix 5000 software version 20 or
Logix Designer application version 21 or later. You need to register the
PowerMonitor 5000 EDS file on the computer on which software project
development is done.
The PowerMonitor 5000 device class is displayed under ‘Unknown Device Type
146’ when adding a new EtherNet module.
1.
Select the desired device and click Create.
2.
Enter the name and IP address of the power monitor.
3.
In the module definition, select Compatible Module and enter the correct
major and minor revisions.
There are three choices for the connection type.
PowerMonitor 5000 Unit Exclusive Owner Connection
The Exclusive Owner connection provides complete control of a PowerMonitor
5000 unit to a Logix controller. When you first set up an Exclusive Owner
connection, the following module-defined controller tags are created:
•
Configuration.Instance table
•
table
•
ScheduledData.Output table
IMPORTANT
If a connection returns an error code 16#0203 Connection timed out, please
refer to Answer 63904 in the Rockwell Automation Knowledgebase.