Cip base energy object – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 217
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
217
Communication
Chapter 9
CIP Base Energy Object
The PowerMonitor 5000 unit supports the following attributes and services of
the Base Energy Object, Class Code 0x4E.
Table 34 - Supported Attributes
Energy Object Attribute ID
Need in Implementation
Access Rule
Energy Object Attribute Name PowerMonitor 5000
Implementation
1
Required
Get
Energy/Resource Type
Supported
2
Required
Get
Energy Object Capabilities
Supported
3
Required
Get
Energy Accuracy
Supported
4
Optional
Get/Set
Energy Accuracy Basis
Get only
5
Conditional
Get/Set
Full Scale Reading
Not needed
6
Optional
Get
Device Status
Not supported
7
Optional
Get
Consumed Energy Odometer
Supported
8
Optional
Get
Generated Energy Odometer
Supported
9
Conditional Get
Total
Energy
Odometer
Supported
10
Conditional Get
Energy
Transfer
Rate
Supported
11
Optional
Set
Energy Transfer Rate User Setting
Not applicable
12
Required
Get
Energy Type Specific Object Path
Supported
13-14
Optional
Set
Energy Aggregation Paths
Not needed
15
Optional
Set
Energy Identifier
Returns Device_Name
16
Optional
Set
Odometer Reset Enable
Not supported
17
Conditional
Get
Metering State
Supported
Table 35 - Supported Services
Energy Service Code
Need in Implementation
Service Name
PowerMonitor 5000
Implementation
Class
Instance
01hex
Optional
Optional
Get_Attributes_All
Supported
03hex
Optional
Optional
Get_Attribute_List
Supported
04hex
N/A
Optional
Set_Attribute_List
Not supported
05hex
Optional
Required
Reset
Not supported
08hex
Optional
N/A
Create
Not supported
09hex
N/A
Optional
Delete
Not supported
0Ehex
Conditional
Required
Get_Attribute_Single
Supported
10hex
N/A
Required
Set_Attribute_Single
Supported
18hex
N/A
Optional
Get_Member
Not supported
19hex
N/A
Optional
Set_Member
Not supported