Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 283

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
283
PowerMonitor 5000 Unit Data Tables
Appendix A
23
Real
IEEE1159_Voltage_Imbalance_Limit_%
The percent of voltage Imbalance to create an imbalance event
3
1.00…10.00
24
Real
IEEE1159_Current_Imbalance_Limit_%
The percent of current Imbalance to create an imbalance event
25
1.00…50.00
25
Real
IEEE1159_DCOffset_Harmonic_Avg_Intvl_m
The a rolling average interval for DC offset and Harmonics in
minutes
5
1…15
26
Real
IEEE1159_Voltage_DCOffset_Limit_%
The percent of DC offset limitation
0.1
0.00…1.00
27
Real
IEEE1159_Voltage_THD_Limit_%
The percent of voltage THD limitation
5
0.00…20.00
28
Real
IEEE1159_Current_THD_Limit_%
The percent of current THD limitation
10
0.00…20.00
29
Real
IEEE1159_PowerFrequency_Avg_Intvl_s
The rolling average interval for power frequency in seconds.
1
1…10
30
Real
IEEE1159_PowerFrequency_Limit_Hz
The limitation on power frequency variation in Hz.
0.1
0.1…0.2
31
Real
IEEE1159_PowerFrequency_Hysteresis_Hz
Hysteresis of power frequency
0.02
0.01…0.05
32
Real
IEEE519_Compliance_Parameter
IEEE 519 Compliance Parameter
0 = Current
1= Voltage
0
0…1
33
Real
IEEE519_MAX_Isc_Amps
Short circuit current available at the point of common coupling.
(PCC) IMPORTANT: When Isc is ‘0’ or IL is ‘0’, the first row in IEEE 519
Current Distortion Limits table is selected for compliance.
0
0.00…1,000,000.0
0
34
Real
IEEE 519 MAX_IL_Amps
Average maximum demand for current for the preceding 12
months. IMPORTANT: When IL is ‘0’ the current THD instead of TDD is
used for compliance.
0
0.00…1,000,000.0
0
35 … 49
Real
Reserved
Reserved for future use.
0
0
Table 78 - Configuration.PowerQuality Data Table
Element
Number
Type
Tag Name
Description
Default
Range