Powerquality.ieee519_ results (m6 model) – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 359
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
359
PowerMonitor 5000 Unit Data Tables
Appendix A
PowerQuality.IEEE519_ Results (M6 model)
The PowerMonitor 5000 M6 model returns short- and long-term rolling average
harmonic distortion data for the fundamental and the first 40 harmonic
frequencies. These results are presented in six similar data tables.
These tables share the following properties.
The IEEE519 Results data tables share a common structure. In the data table
template shown, substitute the following into the Data Table Name and Tag
Name strings to obtain the specific names:
•
For ‘
•
For ‘
For example, the tag CH3_5th_Harmonic_IEEE519_ShortTerm in the
PowerQuality.IEEE519_CH3 _ShortTerm_Results table returns the short-term
5th harmonic value for Channel 3.
Table 185 - Table Properties
Data Table Name
CIP Instance
Number
PCCC File No.
PowerQuality.IEEE519_CH1_ShortTerm_Results
895
F104
PowerQuality.IEEE519_CH2_ShortTerm_Results
896
F105
PowerQuality.IEEE519_CH3_ShortTerm_Results
897
F106
PowerQuality.IEEE519_CH1_LongTerm_Results
898
F107
PowerQuality.IEEE519_CH2_LongTerm_Results
899
F108
PowerQuality.IEEE519_CH3_LongTerm_Results
900
F109
No. of Elements
44
Length in Words
88
Data Type
Real
Data Access
Read Only
IMPORTANT
Channel assignments are based on the value of the tag
IEEE519_Compliance_Parameter found in the Configuration.Power_Quality
table.
IEEE519_Compliance_Parameter
Channel 1
Channel 2
Channel 3
0 = Current
I1
I2
I3
1 = Voltage (Wye and Split Phase)
V1-N
V2-N
V3-N
1 = Voltage (Delta)
V1-V2
V2-V3
V3-V1