Status.wiring_diagnostics – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 297

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
297
PowerMonitor 5000 Unit Data Tables
Appendix A
Status.Wiring_Diagnostics
Table 109 - Table Properties
CIP Instance Number
829
PCCC File Number
F38
No. of Elements
33
Length in Words
66
Data Type
Real
Data Access
Read Only
Table 110 - Status.Wiring_Diagnostics Data Table
Element
Number
Type
Tag Name
Description
Range
0
Real
Command_Status
This is the wiring diagnostics command status.
0 = Command Active
1 = Input Level Low
2 = Disabled
3 = Waiting Command
0…3
1
Real
Voltage_Input_Missing
Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
-1…123
2
Real
Current_Input_Missing
Reports on all three phase.
-1 = Test not run
0 = Test passed
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
-1…123
3
Real
Range1_L97_C89_Status
This is the pass fail status for Range 1 diagnostics.
0 = Pass
1 = Failed
0 or 1
4
Real
Range1_Voltage_Input_Inverted
Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123