Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 298

298
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
5
Real
Range1_Current_Input_Inverted
Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
6
Real
Range1_Voltage_Rotation
Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…132
7
Real
Range1_Current_Rotation
Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…321
8
Real
Range2_L85_C98_Status
This is the pass fail status for Range 1 diagnostics.
0 = Pass
1 = Failed
0 or 1
9
Real
Range2_Voltage_Input_Inverted
Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
10
Real
Range2_Current_Input_Inverted
Reports on all three phases.
-1 = Test not run
0 = Test passed
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
-1…123
11
Real
Range2_Voltage_Rotation
Reports on all three phases. The reported sequence represents each phase.
1…321 designating phase and rotation.
Example: 123 = Phase 1 then phase 2 then phase 3
-1 = Test not run
4 = Invalid Rotation
5 = Out of range
-1…132
Table 110 - Status.Wiring_Diagnostics Data Table
Element
Number
Type
Tag Name
Description
Range