Loggingresults.setpoint_log – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 343
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
343
PowerMonitor 5000 Unit Data Tables
Appendix A
LoggingResults.Setpoint_Log
Table 157 - Table Properties
CIP Instance Number
858
PCCC File Number
F67
No. of Elements
18
Length in Words
36
Data Type
Real
Data Access
Read Only
Table 158 - LoggingResults.Setpoint_Log Data Table
Element
Number
Type
Tag Name
Description
Unit
Range
0
Real
Setpoint_Record_Identifier
Used to verify record sequence when returning multiple records.
1…100
1
Real
Setpoint_Timestamp_Year
The year when the record was recorded.
YYYY
2010…2100
2
Real
Setpoint_Timestamp_Mth_Day
The month and day when the record was recorded.
MMDD
11…1231
3
Real
Setpoint_Timestamp_Hr_Min
The hour and minute when the record was recorded.
HHMM
0…2359
4
Real
Setpoint_Timestamp_Sec_ms
The seconds and milliseconds when the record was recorded.
SSms
0…59,999
5
Real
Setpoint_Number
Setpoint number of record.
0…20
6
Real
Setpoint_Status
Setpoint is active (1) or not active (0).
0…1
7
Real
Input_Parameter
Input test parameter of setpoint.
0…105
8
Real
Test_Condition
Test Condition.
0…3
9
Real
Evaluation_Type
Evaluation type for setpoint.
1…3
10
Real
Threshold_Setting
The threshold setting magnitude or percent.
0.000…
10,000,000
11
Real
Hysteresis_Setting
Magnitude or percent
0.000…
10,000,000
12
Real
Assert_Delay
Time delay before actuation.
seconds
0.000…3600
13
Real
Deassert_Delay
Time delay before deassert.
seconds
0.000…3600
14
Real
Output_Source
Output flag or bit.
0…40
15
Real
Output_Action
Configured action when actuated.
0…TBD
16
Real
Accumulated_Time
Total accumulation in seconds.
seconds
0.000…
10,000,000
17
Real
Number_Of_Transitions
Number of transitions from off to on.
0…10,000,000