Logged parameters – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 110

110
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 6
Logging
Logged Parameters
The energy log records a predefined set of parameters. The first record in each
file is a header that indicates the tag name of each parameter. Each subsequent
record is a structure of REAL elements containing the following parameters.
Table 18 - Energy Log Parameters
Element
Tag Name
Description
0
Energy_ Record_Identifier
Internal unique record number
1
Energy_Timestamp_Year
The date and time of the record
2
Energy_Timestamp_Mth_Day
3
Energy_Timestamp_Hr_Min
4
Energy_Timestamp Sec_ms
5
Status_1_Count_xM
Scaled Status input 1 counter
6
Status_1_Count_x1
7
Status_2_Count_xM
Scaled Status input 2 counter
8
Status_2_Count_x1
9
Status_3_Count_xM
Scaled Status input 3 counter
10
Status_3_Count_x1
11
Status_4_Count_xM
Scaled Status input 4 counter
12
Status_4_Count_x1
13
GWh_Fwd
Forward real energy
14
kWh_Fwd
15
GWh_Rev
Reverse real energy
16
kWh_Rev
17
GWh_Net
Net real energy
18
kWh_Net
19
GVARH_Fwd
Forward reactive energy
20
kVARh_Fwd
21
GVARH_Rev
Reverse reactive energy
22
kVARh_Rev
23
GVARH_Net
Net reactive energy
24
kVARh_Net
25
GVAh
Net apparent energy
26
kVAh
27
kW_Demand
The average real, reactive, apparent power and power
factor during the last demand period
28
kVAR_Demand
29
kVA_Demand
30
Demand_PF
31
Projected_kW_Demand
The projected average real, reactive and apparent
power for the current demand period
32
Projected_kVAR_Demand
33
Projected_kVA_Demand