PowerMonitor 5000 Unit Data Tables
18 Real
Status_Input_1_Input_Scale
When
a status pulse is received the count is increased by the scale factor.
(Input pulse * input scale) added to total status count.
1
1…
1,000,000
19 Real
Status_Input_2_Input_Scale
When
a status pulse is received the count is increased by the scale factor.
(Input pulse * input scale) added to total status count.
1
1…
1,000,000
20 Real
Status_Input_3_Input_Scale
When
a status pulse is received the count is increased by the scale factor.
(Input pulse * input scale) added to total status count.
1
1…
1,000,000
21 Real
Status_Input_4_Input_Scale
When
a status pulse is received the count is increased by the scale factor.
(Input pulse * input scale) added to total status count.
1
1…
1,000,000
22
Real
Unit_Error_Action
This parameter determines the action when a unit error occurs.
0 = Safe Mode on error and make status LED solid red
1 = Perform a firmware reset.
1
0…1
23
Real
Software_Error_Log_Full_Action
This parameter determines the action when a firmware failure is detected and the
error log is full.
0 = Safe Mode on error, make status LED solid red and wait for error collection and
clear log command.
1 = Perform a firmware reset.
1
0…1
24
Real
Default_KYZ_State_On_Comm_
Loss
The Default output state on communication loss defines the behavior of the output if
the power monitor experiences a loss of communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local control
0
0…4
25
Real
Default_Relay_1_State_On_
Comm_Loss
The Default output state on communication loss defines the behavior of the output if
the power monitor experiences a loss of communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local control
0
0…4
26
Real
Default_Relay_2_State_On_
Comm_Loss
The Default output state on communication loss defines the behavior of the output if
the power monitor experiences a loss of communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local control
0
0…4
27
Real
Default_Relay_3_State_On_
Comm_Loss
The Default output state on communication loss defines the behavior of the output if
the power monitor experiences a loss of communication.
0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
4 = Local control
0
0…4
28…49
Real
Reserved
Future Use
0
0
Table 56 - Configuration.System.General Data Table
Element
Number
Type
Tag Name
Description
Default
Range