Rockwell Automation Publication 1426-UM001F-EN-P - November 2013

279

PowerMonitor 5000 Unit Data Tables

Appendix A

Configuration.Data_Log

Table 73 - Table Properties

CIP Instance Number

813

PCCC File Number

N22

No. of Elements

34

Length in Words

34

Data Type

Int16

Data Access

Read/Write

Table 74 - Configuration.Data_Log Data Table

Element
Number

Type

Tag Name
(default tag name)

Description

Default

Range

0

Int16

Data_Logging_Interval

Logging Interval in seconds.
0=Disables data logging
-1= synchronize log with demand period

900 (15 min)

-1…3600

1

Int16

Logging Mode

Selects how records are saved.
0= Fill and stop recording when log is full
1= Overwrite when log is full starting with the earliest record.

1

0…1

2

Int16

DataLog_Parameter_1
(Avg_V_N_Volts)

Selection of parameter or default to be logged in the data log.

5

0…88 (M5)
1…184 (M6)

3

Int16

DataLog_Parameter_2
(Avg_VL_VL_Volts)

Selection of parameter or default to be logged in the data log.

9

0…88 (M5)
1…184 (M6)

4

Int16

DataLog_Parameter_3
(Avg_Amps)

Selection of parameter or default to be logged in the data log.

14

0…88 (M5)
1…184 (M6)

5

Int16

DataLog_Parameter_4
(Avg_Frequency_Hz)

Selection of parameter or default to be logged in the data log.

15

0…88 (M5)
1…184 (M6)

6

Int16

DataLog_Parameter_5
(Total_kW)

Selection of parameter or default to be logged in the data log.

19

0…88 (M5)
1…184 (M6)

7

Int16

DataLog_Parameter_6
(Total_kVAR)

Selection of parameter or default to be logged in the data log.

23

0…88 (M5)
1…184 (M6)

8

Int16

DataLog_Parameter_7
(Total_kVA)

Selection of parameter or default to be logged in the data log.

27

0…88 (M5)
1…184 (M6)

9

Int16

DataLog_Parameter_8
(Total_PF_Lead_Lag_Indicator)

Selection of parameter or default to be logged in the data log.

39

0…88 (M5)
1…184 (M6)

10

Int16

DataLog_Parameter_9
(Avg_True_PF)

Selection of parameter or default to be logged in the data log.

31

0…88 (M5)
1…184 (M6)

11

Int16

DataLog_Parameter_10
(Avg_Disp_PF)

Selection of parameter or default to be logged in the data log.

35

0…88 (M5)
1…184 (M6)

12

Int16

DataLog_Parameter_11
(Avg_IEEE_THD_V_%)

Selection of parameter or default to be logged in the data log.

54

0…88 (M5)
1…184 (M6)

13

Int16

DataLog_Parameter_12
(Avg_IEEE_THD_V_V_%)

Selection of parameter or default to be logged in the data log.

58

0…88 (M5)
1…184 (M6)

14

Int16

DataLog_Parameter_13
(Avg_IEEE_THD_I_%)

Selection of parameter or default to be logged in the data log.

63

0…88 (M5)
1…184 (M6)

15

Int16

DataLog_Parameter_14
(Avg_IEC_THD_V_%)

Selection of parameter or default to be logged in the data log.

68

0…88 (M5)
1…184 (M6)