Configuration.data_log – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 279
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
279
PowerMonitor 5000 Unit Data Tables
Appendix A
Configuration.Data_Log
Table 73 - Table Properties
CIP Instance Number
813
PCCC File Number
N22
No. of Elements
34
Length in Words
34
Data Type
Int16
Data Access
Read/Write
Table 74 - Configuration.Data_Log Data Table
Element
Number
Type
Tag Name
(default tag name)
Description
Default
Range
0
Int16
Data_Logging_Interval
Logging Interval in seconds.
0=Disables data logging
-1= synchronize log with demand period
900 (15 min)
-1…3600
1
Int16
Logging Mode
Selects how records are saved.
0= Fill and stop recording when log is full
1= Overwrite when log is full starting with the earliest record.
1
0…1
2
Int16
DataLog_Parameter_1
(Avg_V_N_Volts)
Selection of parameter or default to be logged in the data log.
5
0…88 (M5)
1…184 (M6)
3
Int16
DataLog_Parameter_2
(Avg_VL_VL_Volts)
Selection of parameter or default to be logged in the data log.
9
0…88 (M5)
1…184 (M6)
4
Int16
DataLog_Parameter_3
(Avg_Amps)
Selection of parameter or default to be logged in the data log.
14
0…88 (M5)
1…184 (M6)
5
Int16
DataLog_Parameter_4
(Avg_Frequency_Hz)
Selection of parameter or default to be logged in the data log.
15
0…88 (M5)
1…184 (M6)
6
Int16
DataLog_Parameter_5
(Total_kW)
Selection of parameter or default to be logged in the data log.
19
0…88 (M5)
1…184 (M6)
7
Int16
DataLog_Parameter_6
(Total_kVAR)
Selection of parameter or default to be logged in the data log.
23
0…88 (M5)
1…184 (M6)
8
Int16
DataLog_Parameter_7
(Total_kVA)
Selection of parameter or default to be logged in the data log.
27
0…88 (M5)
1…184 (M6)
9
Int16
DataLog_Parameter_8
(Total_PF_Lead_Lag_Indicator)
Selection of parameter or default to be logged in the data log.
39
0…88 (M5)
1…184 (M6)
10
Int16
DataLog_Parameter_9
(Avg_True_PF)
Selection of parameter or default to be logged in the data log.
31
0…88 (M5)
1…184 (M6)
11
Int16
DataLog_Parameter_10
(Avg_Disp_PF)
Selection of parameter or default to be logged in the data log.
35
0…88 (M5)
1…184 (M6)
12
Int16
DataLog_Parameter_11
(Avg_IEEE_THD_V_%)
Selection of parameter or default to be logged in the data log.
54
0…88 (M5)
1…184 (M6)
13
Int16
DataLog_Parameter_12
(Avg_IEEE_THD_V_V_%)
Selection of parameter or default to be logged in the data log.
58
0…88 (M5)
1…184 (M6)
14
Int16
DataLog_Parameter_13
(Avg_IEEE_THD_I_%)
Selection of parameter or default to be logged in the data log.
63
0…88 (M5)
1…184 (M6)
15
Int16
DataLog_Parameter_14
(Avg_IEC_THD_V_%)
Selection of parameter or default to be logged in the data log.
68
0…88 (M5)
1…184 (M6)