Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 304
304
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
6
Int16
Logs_Status
Logs Condition Status
0… 65,535
Bit 0
Data_Log_Full_Fill_And_Stop
Is Set when fill and stop is configured and log is at least 80% filled
0…1
Bit 1
Event_Log_Full_Fill_And_Stop
Is Set when fill and stop is configured and log is at least 80% filled
0…1
Bit 2
Setpoint_Log_Full_Fill_And_Stop
Is Set when fill and stop is configured and log is at least 80% filled
0…1
Bit 3
PowerQuality_Log_Full_Fill_And_Stop
Is Set when fill and stop is configured and log is at least 80% filled
0…1
Bit 4
Energy_Log_Full_Fill_And_Stop
Is Set when fill and stop is configured and log is at least 80% filled
0…1
Bit 5
Waveform_Full
Is Set when log is at least 80% filled
0…1
Bit 6
TriggerData_Full_Fill_And_Stop
Is Set when fill and stop is configured and log is at least 80% filled
0…1
Bit 7…15
Reserved
Reserved for future use
0
7
Int16
Output_Pulse_Overrun
The output pulse rate exceeds the configured capability
0
Bit 0
KYZ_Pulse_Overrun
The KYZ output pulse rate exceeds the configured capability
Bit 1
Relay1_Pulse_Overrun
The Relay 1 output pulse rate exceeds the configured capability
Bit 2
Relay2_Pulse_Overrun
The Relay 2 output pulse rate exceeds the configured capability
Bit 3
Relay3_Pulse_Overrun
The Relay 3 output pulse rate exceeds the configured capability
Bit 4…15
Reserved
Reserved for future use
8
Int16
IEEE1159_Over_Voltage
Over Voltage Condition
0…65535
Bit 0
IEEE1159_Over_Voltage_V1
1 = An over voltage is detected on V1
0…1
Bit 1
IEEE1159_Over_Voltage_V2
1 = An over voltage is detected on V2
0…1
Bit 2
IEEE1159_Over_Voltage_V3
1 = An over voltage is detected on V3
0…1
Bit 3... 15
Reserved
Reserved for future use
0
9
Int16
IEEE1159_Under_Voltage
Under Voltage Condition
0…65535
Bit 0
IEEE1159_Under_Voltage_V1
1 = An under voltage is detected on V1
0…1
Bit 1
IEEE1159_Under_Voltage_V2
1 = An under voltage is detected on V2
0…1
Bit 2
IEEE1159_Under_Voltage_V3
1 = An under voltage is detected on V3
0…1
Bit 3... 15
Reserved
Reserved for future use
0
10
Int16
IEEE1159_Imbalance_Condition
IEEE1159 Imbalance
0…65535
Bit 0
IEEE1159_Imbalance_Condition_Volts
1 = An Imbalance is detected on Voltage
0…1
Bit 1
IEEE1159_Imbalance_Condition_Current
1 = An Imbalance is detected on Current
0…1
Bit 2...15
Reserved
Reserved for future use
0
11
Int16
IEEE1159_DCOffset_Condition
IEEE1159 DC Offset Condition
0…65535
Bit 0
IEEE1159_DCOffset_Condition_V1
1 = A DC offset exceed limitation is detected on V1
0…1
Bit 1
IEEE1159_DCOffset_Condition_V2
1 = A DC offset exceed limitation is detected on V2
0…1
Bit 2
IEEE1159_DCOffset_Condition_V3
1 = A DC offset exceed limitation is detected on V3
0…1
Bit 3... 15
Reserved
Reserved for future use
0
12
Int16
IEEE1159_Voltage_THD_Condition
IEEE1159 Voltage THD Condition
0…65535
Bit 0
IEEE1159_Voltage_THD_Condition_V1
1 = A THD exceed limitation is detected on V1
0…1
Bit 1
IEEE1159_Voltage_THD_Condition_V2
1 = A THD exceed limitation is detected on V2
0…1
Bit 2
IEEE1159_Voltage_THD_Condition_V3
1 = A THD exceed limitation is detected on V3
0…1
Bit 3... 15
Reserved
Reserved for future use
0
Table 116 - Status.Alarms Data Table
Element
Number
Type
Tag Name
Description
Range