Once security is enabled and an Admin class account is set up during initial
configuration, the remaining security configuration can be done through the
network web page.
If you want to configure power monitors by using software, such as FactoryTalk
EnergyMetrix RT software, set up at least one Application class account.
This table summarizes the security classes, privileges, access, and limits that apply
to the PowerMonitor 5000 unit.
The following rules further define security operation:
•
The USB Admin account can be accessed only through the web page when
connected via USB.
•
Only one Admin can be active at a time, including the USB Admin class.
•
A logged in account remains active until logged out or until 30 minutes has
elapsed without writing a configuration parameter. FTP access to log files
remains until the account is logged out.
•
Only an Admin class account can add, remove, or edit accounts. An
Admin class account cannot delete itself and the default USB Admin
account cannot be deleted.
•
An Application class account is used for access by using CIP or PCCC
protocols via native Ethernet network or optional DeviceNet network
communication. An Application class account logs in by writing its
username to the
table and then its password to the
table within 30 seconds. An application can obtain
security status information by reading the
data table.
Table 30 - Account Classes and Privileges
Account Class
Privileges
Interface
Maximum Number of Accounts
USB admin
Manage security accounts
Read data
Write configuration parameters
Download log files
USB only web page
1
Admin
Manage security accounts
Read data
Write configuration parameters
Download log files
USB and native Ethernet web page
10
User
Read data
Download log files
USB and native Ethernet web page
20
Application
Read data
Write configuration parameters
Download log files
Native EtherNet/IP and optional DeviceNet
communication CIP assembly and
parameters objects CSP/PCCC data tables
10
privileges with security disabled (all)
Read data
Write configuration parameters
Download log files
Any
-
security enabled but no user logged in
Read data
Any
-