Configuration.triggersetpointinfofile (m6 model), Configuration.triggerdata(m6 model) – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 287

Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
287
PowerMonitor 5000 Unit Data Tables
Appendix A
Configuration.TriggerSetpointInfoFile (M6 model)
Configuration.TriggerData(M6 model)
Table 89 - Table Properties
CIP Instance Number
865
PCCC File Number
ST74
No. of Elements
1
Length in Words
32
Data Type
String
Data Access
Write Only
Table 90 - Configuration.TriggerSetpointInfoFile Data Table
Element
Number
Type
Tag Name
Description
Default
Range
0
String
Trigger_Setpoio
nt_Log_File
A single entry table for a 64 character Filename entry
0
64 bytes
Table 91 - Table Properties
CIP Instance Number
822
PCCC File Number
N31
No. of Elements
10
Length in Words
10
Data Type
Int16
Data Access
Read/Write
Table 92 - Configuration.TriggerData Data Table
Element
Number
Type
Tag Name
Description
Default
Range
0
Int16
Trigger_Mode
Selects how records are saved. 0= Fill and stop recording when log is full. 1= Overwrite
when log is full starting with the earliest record.
1
0…1
1
Int16
TriggerData_Length_s
TriggerData log length from 1s to 10s
1s
1…10s
2
Int16
TriggerData_Parameter_1
Selection of parameter or default to be logged in the trigger data log.
5
1…184
3
Int16
TriggerData_Parameter_2
9
1…184
4
Int16
TriggerData_Parameter_3
14
1…184
5
Int16
TriggerData_Parameter_4
15
1…184
6
Int16
TriggerData_Parameter_5
19
1…184
7
Int16
TriggerData_Parameter_6
23
1…184
8
Int16
TriggerData_Parameter_7
27
1…184
9
Int16
TriggerData_Parameter_8
39
1…184