Chapter 9
Communication
Communication Command
Summary
This section lists the commands supported by each communications network
type.
EtherNet/IP Network
•
CIP Generic Assembly Object (Class 04), Get & Set Attribute Single for
Attribute 3 (data)
•
CIP Generic Assembly Object (Class 04), Get Attribute Single for
Attribute 4 (size)
•
PCCC PLC5 Word Range Write Function (CMD = 0x0F, FUNC =
0x00)
•
PCCC PLC5 Word Range Read Function (CMD = 0x0F, FUNC =
0x01)
•
PCCC PLC5 Typed Write Function (CMD = 0x0F, FUNC = 0x67)
•
PCCC PLC5 Typed Read Function (CMD = 0x0F, FUNC = 0x68)
•
PCCC Protected Logical Read Function w/2 Address Fields (CMD =
0x0F, FUNC = 0xA1)
•
PCCC Protected Logical Write Function w/2 Address Fields (CMD =
0x0F, FUNC = 0xA9)
•
PCCC Protected Logical Read Function w/3 Address Fields (CMD =
0x0F, FUNC = 0xA2)
•
PCCC Protected Logical Write Function w/3 Address Fields (CMD =
0x0F, FUNC = 0xAA)
•
PCCC Status Diagnostics (CMD = 0x06, FUNC = 0x03)
DeviceNet and ControlNet Network
•
CIP Generic Assembly Object (Class 04), Get & Set Attribute Single for
Attribute 3 (data)
•
PCCC PLC5 Word Range Write Function (CMD = 0x0F, FUNC =
0x00)
•
PCCC PLC5 Word Range Read Function (CMD = 0x0F, FUNC =
0x01)
•
PCCC PLC5 Typed Write Function (CMD = 0x0F, FUNC = 0x67)
•
PCCC PLC5 Typed Read Function (CMD = 0x0F, FUNC = 0x68)
•
PCCC Protected Logical Read Function w/2 Address Fields (CMD =
0x0F, FUNC = 0xA1)
•
PCCC Protected Logical Write Function w/2 Address Fields (CMD =
0x0F, FUNC = 0xA9)
•
PCCC Protected Logical Read Function w/3 Address Fields (CMD =
0x0F, FUNC = 0xA2)
•
PCCC Protected Logical Write Function w/3 Address Fields (CMD
=0x0F, FUNC = 0xAA)
•
PCCC Status Diagnostics (CMD = 0x06, FUNC = 0x03)