Logged parameters – Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 120
120
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Chapter 6
Logging
Logged Parameters
The data log records a user-selected set of parameters. The first record in each file
is a header that indicates the tag name of each logged parameter. Each subsequent
record is a structure of REAL elements containing the following parameters.
Table 20 - Data Log Logged Parameters
Element
Tag Name
Description
0
Data_ Record_Identifier
Data log record time stamp
1
Data _Timestamp_Year
2
Data _Timestamp_Mth_Day
3
Data _Timestamp_Hr_Min
4
Data _Timestamp Sec_ms
5
DataLog_Parameter_1
(Avg_V_N_Volts)
Values of user-selected or default
parameters (Default parameter
selection tag name)
6
DataLog_Parameter_2
(Avg_VL_VL_Volts)
7
DataLog_Parameter_3 (Avg_Amps)
8
DataLog_Parameter_4
(Avg_Frequency_Hz)
9
DataLog_Parameter_5 (Total_kW)
10
DataLog_Parameter_6 (Total_kVAR)
11
DataLog_Parameter_7 (Total_kVA)
12
DataLog_Parameter_8
(Total_PF_Lead_Lag_Indicator)
13
DataLog_Parameter_9
(Avg_True_PF)
14
DataLog_Parameter_10
(Avg_Disp_PF)
15
DataLog_Parameter_11
(Avg_IEEE_THD_V_%)
16
DataLog_Parameter_12
(Avg_IEEE_THD_V_V_%)
17
DataLog_Parameter_13
(Avg_IEEE_THD_I_%)
18
DataLog_Parameter_14
(Avg_IEC_THD_V_%)
19
DataLog_Parameter_15
(Avg_IEC_THD_V_V_%)
20
DataLog_Parameter_16
(Avg_IEC_THD_I_%)
21
DataLog_Parameter_17
(Voltage_Unbalance_%)
22
DataLog_Parameter_18
(Current_Unbalance_%)
23
DataLog_Parameter_19
24
DataLog_Parameter_20