Rockwell Automation 1426 PowerMonitor 5000 Unit User Manual
Page 330

330
Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A
PowerMonitor 5000 Unit Data Tables
29
Real
L3_kVA
L3 apparent power
kVA
0…9.999E15
30
Real
Total_kVA
Total apparent power
kVA
0…9.999E15
31
Real
L1_True_PF_%
L1 true power factor (full bandwidth)
%
0.00…100.00
32
Real
L2_True_PF_%
L2 true power factor (full bandwidth)
%
0.00…100.00
33
Real
L3_True_PF_%
L3 true power factor (full bandwidth)
%
0.00…100.00
34
Real
Avg_True_PF
Average true power factor
%
0.00…100.00
35
Real
L1_Disp_PF
L1 displacement power factor (fundamental only)
%
0.00…100.00
36
Real
L2_Disp_PF
L2 displacement power factor (fundamental only)
%
0.00…100.00
37
Real
L3_Disp_PF
L3 displacement power factor (fundamental only)
%
0.00…100.00
38
Real
Avg_Disp_PF
Average displacement power factor (fundamental only)
%
0.00…100.00
39
Real
L1_PF_Lead_Lag_Indicator
L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
40
Real
L2_PF_Lead_Lag_Indicator
L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
41
Real
L3_PF_Lead_Lag_Indicator
L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
42
Real
Total_PF_Lead_Lag_Indicator
L1 lead or lag indicator for power factor
1 = leading
-1 = lagging
-1…1
43
Real
Voltage Rotation
Voltage rotation has the following designations:
0 = Not metering
123 = ABC rotation
132 = ACB rotation
4 = No rotation
0…132
44
Real
Metering_Iteration
A number 0…9999999 that indicates that the metering
functions and internal communication are updating
0…9,999,999
45…55
Real
Resvd
Reserved
Table 136 - MeteringResults.RealTime_VIF_Power Data Table
Element
Number
Type
Tag Name
Description
Units
Range